Server rack planner that checks the power, heat and weight too

Lay out a 19-inch rack device by device and see, as you type, whether the cabinet still fits, whether the circuit holds, how much heat you have to move, and what size UPS keeps it alive. Nothing is sent anywhere.

Free no account Private runs in your browser Offline after first load Export CSV, JSON, print

Rack and supply

inputs
A
%
Nameplate watts are a maximum; real draw is lower.
/kWh
mm
kg
°C
Rise across the rack you accept.
0.9 is typical for switching supplies.
Wh
0 hides the runtime estimate.

Add equipment

presets

Custom device

U
W
kg
mm

Blank and spacer rows are real devices with 0 W — they keep gaps in the elevation honest.

Rack elevation

U1 at the bottom
Server Network Storage Power AV Accessory

Device detail

nameplate
U Device Cat U W kg mm

What to fix before you buy

How the numbers are worked out

Every figure below is arithmetic you can check by hand. No algorithms are hidden and nothing is fetched from a server.

Space

One rack unit is 44.45 mm (1.75 in). Used space is the sum of device heights; free space is the rack height minus that sum. A device that does not fit is refused rather than silently overflowing.

Power and circuit

Current equals watts divided by volts. Continuous loads are limited to 80% of the breaker rating, so the planner compares draw against breaker × 0.8 and flags anything above it.

Heat and airflow

Drawn power becomes heat: BTU/h = W × 3.412. Airflow to remove it is about 3.16 CFM per watt per °F of accepted rise, which is 2.98 m³/h per watt per °C.

UPS

Apparent power is W / power factor; the planner recommends 25% headroom above that. Runtime assumes 85% inverter efficiency and 60% usable battery depth.

What this is not: a substitute for a licensed electrician, a thermal survey or a manufacturer's rail-depth check. It is a planning estimate built from nameplate figures. Confirm final loads against real measured draw before committing.

Questions

What is a rack unit (U)?

One rack unit equals 44.45 mm (1.75 inches) of vertical space. A standard full-height rack is 42U; network cabinets are commonly 12U to 24U. Device heights are quoted in whole U so the elevation always adds up exactly.

How much power can a server rack draw from one circuit?

A continuous load must not exceed 80% of the breaker rating. On a 120 V 15 A circuit that is 12 A (~1,440 W); on 120 V 20 A it is 16 A (~1,920 W); on 230 V 16 A it is 12.8 A (~2,944 W). The planner compares your total nameplate draw against the breaker you choose and warns when you cross that line.

How do I calculate the heat load of a rack?

Essentially all electrical power drawn by IT equipment becomes heat: BTU per hour equals watts multiplied by 3.412. The airflow needed to carry that heat away depends on the temperature rise you accept across the equipment, using the standard relationship of about 3.16 CFM per watt per degree Fahrenheit of rise.

What size UPS does a rack need?

Convert real power to apparent power by dividing watts by the power factor (about 0.9 for modern switching supplies), then add 25% headroom so the UPS runs below full load. Runtime is governed by battery capacity, so this planner asks for battery watt-hours and reports an estimated runtime that assumes 85% inverter efficiency and 60% usable battery depth.